Power rating | 240 W |
---|
Output voltage | 24 VDC |
---|
Efficiency | 85 % typ. (at 100 VAC input) 88 % typ. (at 200 VAC input) |
---|
Input | Rated input voltage | 100 to 240 VAC |
---|
Allowable input voltage variable range | 85 to 264 VAC 80 to 370 VDC |
---|
Frequency | 50/60Hz (47 to 63 Hz) |
---|
Rated input current | 3.8 A max., 2.9 A typ. (at 100 VAC input) 2.0 A max., 1.5 A typ. (at 200 VAC input) |
---|
Power factor | 0.9 min. |
---|
Leakage current | 0.5 mA max. (at 100 VAC input) 1.0 mA max. (at 200 VAC input) |
---|
Inrush current (cold start at 25 ℃) | 17.5 A max., 14 A typ. (at 100 VAC input) 35 A max., 28 A typ. (at 200 VAC input) |
---|
Output | Rated output current | 10 A |
---|
Output voltage variable range | -10 to +15 % With V.ADJ |
---|
Ripple | 160 mV max. |
---|
Static input variation influence | 0.5 % max. (at 100% load) |
---|
Static load variation influence | 1.5 % max. (at rated input, 0 to 100% load) |
---|
Ambient temperature variation influence | 0.05 %/℃ max. |
---|
Start up time | 510 ms typ. (at 100 VAC input) 510 ms typ. (at 200 VAC input) |
---|
Hold time | 46 ms typ. (at 100 VAC input) 46 ms typ. (at 200 VAC input) |
---|
Additional functions | Overload protection | Yes, automatic reset |
---|
Overvoltage protection | Yes, Shut off the input voltage and turn on the input again |
---|
Series operation | Yes (Up to 2 Power Supplies with external diode) |
---|
Parallel operation | No (However, backup operation is possible, external diodes required.) |
---|
Output indicator | Yes (color: green) |
---|
Output voltage indication | Yes (switching) |
---|
Output current indication | Yes (switching) |
---|
Peak-hold current indication | Yes (switching) |
---|
Total run time monitor | Output: Yes (Transistor output, 30 VDC max., 50 mA max) Indication: Yes (switching) |
---|
Undervoltage alarm | Output: Yes (Transistor output, 30 VDC max., 50 mA max) Indication: Yes (switching) |
---|
Insulation | Dielectric strength | Between all input terminals and all output terminals: 3 kVAC for 1 min, Detection current: 20 mA Between all input terminals and PE terminals: 2 kVAC for 1 min, Detection current: 20 mA Between all output terminals and PE terminals: 1 kVAC for 1 min, Detection current: 20 mA |
---|
Insulation resistance | Between all output terminals and all input terminals/ PE terminals: 100 MΩ min., at 500 VDC |
---|
Environment | Vibration resistance | 10 to 55 Hz, 0.375 mm single amplitude in each 3 directions for 2 hours |
---|
Shock resistance | 150 m/s2, in each 6 directions 3 times |
---|
Ambient temperature (Operating) | -10 to 60 ℃ |
---|
Ambient temperature (Storage) | -25 to 65 ℃ |
---|
Ambient humidity (Operating) | 25 to 85 % |
---|
Ambient humidity (Storage) | 25 to 90 % |
---|
Reliability | Life expectancy | 10 years (at rated input, a load rate of 50% load, under the temperature of 40 ℃, standard mounting) |
---|
Construction | Construction | Covered type |
---|
Connection | Terminal blocks |
---|
Terminal type | Screw terminal |
---|
Mounting | DIN track mounting |
---|
Attachment | Terminal block cover |
---|
Weight (Main) | 1150 g max. |
---|