Rated power supply voltage | 200/220/240 VAC 50/60 Hz |
---|
Allowable voltage variable range | 85 to 110% of the power supply voltage |
---|
Input signals | Reset |
---|
Input method | No-voltage input |
---|
No-voltage input | Short-circuit (ON) impedance: 1 kΩ max. Short-circuit (ON) residual voltage: 1 V max. Open circuit impedance: 500 kΩ min. |
---|
Power consumption | Approx. 0.35 VA (at 240 VAC) Approx. 0.3 W (at 240 VAC) |
---|
Operation start voltage | 30% max. of rated supply voltage |
---|
Number of time ranges | 4 |
---|
Operation mode | Power OFF-delay |
---|
Control output (Type) | Time-limit: SPDT |
---|
Control output (Contact output) | Minimum applicable load: 100 mA at 5 VDC (failure level: P Reference value) |
---|
Operating resetting | Instantaneous operation/Time-limit reset/Forced reset |
---|
Ambient temperature range | Operating: -10 to 55 ℃ (with no icing) Storage: -25 to 65 ℃ (with no icing) |
---|
Ambient humidity range | Operating: 35 to 85 % |
---|
Accuracy of operating time | ±0.2% FS max. (±0.2% ±10 ms in a range of 0.6 s and 1.2 s) |
---|
Setting error | ±5% FS ±50 ms max. |
---|
Influence of voltage | ±0.2% FS max. (±0.2% ±10 ms in a range of 0.6 s and 1.2 s) |
---|
Influence of temperature | ±1% FS max. (±1% ±10 ms in a range of 0.6 s and 1.2 s) |
---|
Insulation resistance | 100 MΩ min. (at 500 VDC) |
---|
Dielectric strength | Between current carrying metal parts and non-current carrying metal parts: 2,000 VAC 50/60 Hz 1 min Between control output terminals and operating circuit: 2,000 VAC 50/60 Hz 1 min Between contacts of different polarity: 2,000 VAC 50/60 Hz 1 min Between non-continuous contacts: 1,000 VAC 50/60 Hz 1 min |
---|
Impulse withstand voltage | Between power terminals: 5 kV Between current carrying terminals and exposed non-current carrying metal parts: 5 kV |
---|
Noise immunity | ±1.5 kV (between power terminals) and ±600 V (between input terminals), square-wave noise by noise simulator (pulse width: 100 ns/1 µs, 1-ns rise) |
---|
Static immunity | Mulfunction: 8 kV, Destruction: 15 kV |
---|
Vibration resistance | Destruction: 10 to 55 Hz, 0.75 mm single amplitude each in 3 directions for 2 h Malfunction: 10 to 55 Hz, 0.5 mm single amplitude each in 3 directions for 10 min |
---|
Shock resistance | Destruction: 980 m/s2, 3 times each in 6 directions Malfunction: 98 m/s2, 3 times each in 6 directions |
---|
Life expectancy (relay output) | Electrical: 100,000 operations min. (5 A at 250 VAC, resistive load at 1200 operations/h) Mechanical: 10 million operations min. (under no load at 1,200 operations/h) |
---|
Degree of protection | IP40 (panel surface) |
---|
Connecting method | 8-pin round socket |
---|
Weight | Approx. 120 g |
---|
Applicable socket | P2CF-08/ P2CF-08-E/ PF085A/ P3G-08/ PL08/ PL08-Q/ PLE08-0 |
---|